- Home > Products > Electric Drive > Medium Voltage Drives > SBH Series Medium Voltage Drive
SBH Series Medium Voltage Drive
-
● 4th generation MV drive for general purpose
● 3, 3.3, 6, 6.6, 10, 11kV voltage class
● VF, VF+PG, SVC, closed-loop Vector Control
● Power unit bypass and phase shift technology protection
● 2 drive 1 motor with thermal redundancy technology
● Hot redundancy technology
● 3-full (full load, full voltage, full current) testing
Specifications
- Specifications
- Downloads
Specifications
With advanced vector control technologies including VF, VF+PG, SVC, and closed-loop vector control, the drive ensures precise speed regulation, stable torque output, and improved system response for demanding process control environments.
Key Parameter Ranges & Performance Advantages
Wide Voltage & Power Coverage for Large Industrial Loads
Supports 3-11kV three-phase input voltage and delivers 160kW to 30MW output power range, enabling stable operation for large motors in heavy industries while allowing customization for higher power requirements.
Flexible Output Control for Precise Motor Performance
Provides 0-120Hz output frequency range with 0.01Hz digital frequency resolution, ensuring accurate speed adjustment and energy optimization across different load conditions.
Strong Overload Capacity for Harsh Operating Conditions
Handles 120% overload for 120s, 150% overload for 5s, and 200% instantaneous overload, protecting motors during sudden load impact and improving system reliability.
Ultra-High Efficiency Reduces Operating Costs
Achieves ≥98% inverter efficiency and ≥96.5% total system efficiency, significantly reducing energy consumption and long-term operating expenses.Low Harmonic Distortion for Grid Compatibility
Maintains ≤2% harmonic distortion (IEEE519 compliant), helping protect grid stability and reducing electrical interference in sensitive equipment.
High Power Factor Improves Electrical Utilization
Delivers ≥0.96 power factor, improving power utilization efficiency and lowering reactive power losses.
Advanced Technology & Reliability Design
Voltage Source Inverter Architecture for Stable Output
Uses VSI inverter technology combined with multi-pulse rectifier design (30-pulse / 48-pulse depending on voltage class), ensuring stable output voltage and reduced harmonics.
Redundancy & Bypass Technology Ensures Continuous Operation
Supports power unit bypass, mechanical and electrical bypass, and hot redundancy, reducing downtime and improving system availability for critical industrial processes.
Intelligent Control & Automation Integration
Includes integrated PID control, PLC function modules, multi-step speed control (32 steps), and remote monitoring capability, enabling seamless integration with PLC, DCS, and industrial automation networks.
Flexible Communication & Control Integration
Supports multiple industrial communication options including RS485 Modbus RTU (standard) and optional Profibus-DP, Profinet, Ethernet, Bluetooth, and USB, allowing easy connection with factory automation and IIoT systems.
Industrial-Grade Environmental Adaptability
Operates reliably under -10°C to +40°C working temperature, with storage tolerance from -40°C to +70°C, making it suitable for harsh industrial environments.
Provides customizable enclosure protection levels from IP20 up to IP54, meeting installation requirements across various industrial conditions.
Comprehensive Protection & Safety Functions
Includes full protection features such as over-current, over-voltage, under-voltage, phase loss, motor overload, short circuit, and overheating protection, ensuring long-term safe operation and reducing maintenance risks.
Typical Application Scenarios
The SBH Medium Voltage Drive is widely used in large industrial motor applications including:
Power generation and electric utilities
Mining and metallurgy
Oil and gas processing
Building materials and cement production
Municipal water supply and pumping systems
Heavy industrial OEM equipment
Medium voltage drives are commonly used to improve energy efficiency and system stability in large industrial processes and high-power motor systems.
Why Choose SBH Series Medium Voltage Drive?
Choosing the SBH Series means gaining a high-efficiency, high-reliability, and future-ready motor control solution that helps reduce energy costs, improve production stability, and support intelligent industrial automation upgrades.
If you are looking for a medium voltage drive that balances high power performance, flexible system integration, and long-term operational reliability, the SBH Series is an ideal choice for demanding industrial environments.
|
|
Items |
Descriptions |
|
Input |
Rated voltage, frequency |
3 phase: 3-11kV, 50Hz/60Hz |
|
Allowable range |
Voltage fluctuating range: -20%~15%; voltage unbalance: <3%; frequency: 50/60 ±10% |
|
|
Output |
Output voltage |
Three-phase, 0V~input voltage, tolerance<5% |
|
Output frequency range |
0.00 - 120.00Hz |
|
|
Output power range: |
160-30,000 kW, customized for larger power rating |
|
|
Performance |
Overload capacity |
120% of rated current for 120s |
|
Frequency resolution |
Digital setting: 0.01Hz; |
|
|
Harmonic |
<=2%, meet IEEE519 |
|
|
Technology |
Voltage-source inverter(VSI) |
|
|
Rectifier |
10kV: 48 pulses rectifier, 6kV: 30 pulses rectifier, customize for customer |
|
|
Input voltage drop without reset |
25% |
|
|
Power factor |
>=0.96 |
|
|
Efficiency (Inverter) |
>=98% |
|
|
Total efficiency |
>=96.5% |
|
|
Power cells |
8pcs/phase for 10kv, 9pcs/phase for 11kV. Customized for customer 5pcs/phase for 6kV, 6pcs/phase for 6.6kV, Customized for customer Support mechanical and electrical bypass Electrical and mechanical bypass, optional neutral phase shift bypass |
|
|
Certification |
CE, EAC |
|
|
Output voltage level |
Phase voltage level: 2n+1, line voltage level: 4n+1, n= power cell quantity of each phase |
|
|
Shutdown time upon power loss |
>=300ms |
|
|
Output voltage spike rate |
<1,000v/μs |
|
|
Input/output |
Analog input AI |
3 channels AI: 0/4~20mA, 0-10V |
|
Analog output AO |
4 channels AO: 0/4~20mA, 0-10V |
|
|
Digital input |
14 digital input |
|
|
Digital output |
10 relay output |
|
|
Communication |
Built-in RS485 interface with Modbus RTU, optional for ProfibusDP, Profinet,Bluetooth, USB port, Ethernet |
|
|
Control |
Motor control mode |
VF, VF+PG, SVC, VC+PG |
|
Run command channel |
HMI, control terminal setting, communication setting, PLC, DCS, .etc |
|
|
Frequency setting channel |
HMI, communication, UP/DOWN regulated value, AI, PID, multi-step speed, logic |
|
|
Control power |
1phase 220V, 3kVA, 50/60Hz |
|
|
Acceleration & deceleration |
Linear, S curve ACC/DEC, 0.1-3600 sec |
|
|
Jog |
Jogging frequency range: 0.10Hz~50.00Hz |
|
|
AVR |
Automatic voltage regulation |
|
|
Automatic carrier frequency |
Automatically regulate carrier frequency according to load characteristic and environment temperature |
|
|
Master-Slave |
Optional power balance cabinet |
|
|
Multistep speed method |
32 steps |
|
|
Functions |
Integrated PID, Speed search start, Flying Restart, Load profile, Output power meter, Integrated energy consumption optimization meter, Power loss ride through 2 sets PLC models, |
|
|
Optional |
Bypass cabinet, manually and automatically, |
|
|
Others |
Tracking start, stall prevention, oscillation suppression, accurate dead zone compensation functions |
|
|
Environment |
Protection |
Over-current, over-voltage, under-voltage, phase loss, output interphase short circuit, overheat, |
|
Altitude |
With altitude below 1000m, derate >1000m |
|
|
Operating |
-10~+40℃ / <95%RH, without condensation water drop |
|
|
Storage temperature |
-40~+70℃ |
|
|
Vibration |
<5.9m/s2 (0.6g) |
|
|
Structure |
Degree of protection |
IP20, IP30, IP31, IP41, IP42, IP54 customizable |
|
Bypass cabinet |
Manual and Auto operation mode Rate voltage 7.2/12kV Rate current: Refer to MVD rated specification Shor-time withstand current for 1s 4kA/1s Mechanical life operation 500,000 times, optional 1,000,000 times Opening time ≤30ms Closing time ≤90ms |
|
|
Maintenance |
Single side/double side |
|
|
Power cable input |
Bottom input, bottom output, optional for other | |
|
Temporary lost time |
8 ms |
|
|
Distance from MVD to motor |
>500m |
|
|
Transformer |
Copper/Aluminum, H insulation, with temperature sensor |
|
|
Noise |
<75 dB at 1m distance |
|
|
Cloud service |
Provide cloud service, easy monitoring and remote support |
|
Cooling mode
|
Forced-air cooling, liquid cooling, air-liquid cooling |
|
|
HMI |
Language |
7" English/Chinese, optional other size |
Downloads
| File Name | Type | Language | File Type | Update | Download |
|---|---|---|---|---|---|
| SBH MV Drive _EN-V3.2 | Catalog | English | 2025-06-09 | 4.71MB | |
| SBH H4 Integrated user manual_EN_V4 | Manual | English | 2025-06-09 | 4.96MB | |
| SBH H3.5 Standard user manual_EN_V4 | Manual | English | 2025-06-09 | 4.85MB | |
| SBH H3.5 Standard user manual_EN_V4 | Manual | English | 2025-06-09 | 4.85MB | |
| SBH H4 Integrated user manual_EN_V4 | Manual | English | 2025-06-09 | 4.96MB | |
| SBH Flyer_EN_V1.0 | Catalog | English | 2025-06-09 | 3.7MB | |
| SBH MV Drive _EN-V3.2 | Catalog | English | 2025-06-09 | 4.71MB |
English